Thermocouple Types Explained: K, J, T, E, N, R, S and B Compared
How a thermocouple works, the temperature range of each thermocouple type, colour codes, and how to choose the right one for your process or PLC.
Quick summary: A thermocouple is a temperature sensor made from two different metal wires joined at one end. There are eight common thermocouple types, named by letter. Type K is the general-purpose choice for most industrial work. Type J suits lower temperatures. Type T is best for very cold or food applications. Type E gives the strongest signal. Type N is a more stable alternative to K. Types R, S and B use platinum and are used in furnaces and kilns up to about 1700 Β°C.
Walk through almost any plant, from a bakery oven to a steel furnace, and you will find thermocouples. They are cheap and simple, and they cover a wider temperature range than any other common sensor.
The catch is that there is no single "thermocouple". There are several types of thermocouple, each made from a different pair of metals, and choosing the wrong one gives you poor accuracy, a short sensor life or readings that are simply wrong.
This guide explains how thermocouples work, compares every common type side by side, and shows how to choose and connect one in a real control system.
01 What Is a Thermocouple?
A thermocouple is a temperature sensor made of two wires of different metals joined at one end. When the joined end, called the hot junction or measuring junction, is at a different temperature from the other end, a small voltage appears between the wires. That voltage, measured in millivolts, is used to work out the temperature.
Thermocouples need no external power, respond quickly, and survive vibration and high heat. That is why they are the most widely used temperature sensors in industry.
02 How a Thermocouple Works
Thermocouples work on the Seebeck effect: when two different metals are joined and their junctions are at different temperatures, a voltage is produced. The size of the voltage depends on the metals used and on the temperature difference.
Because the voltage depends on a temperature difference, the instrument also needs to know the temperature at its own terminals, called the cold junction or reference junction. It measures that with a small built-in sensor and adds it back. This is called cold junction compensation (CJC), and every thermocouple transmitter, controller and PLC input card does it automatically.
The signal is tiny. A Type K thermocouple produces only about 41 microvolts per Β°C, which is around 4 mV at 100 Β°C. That is why thermocouple wiring must be kept away from motor cables and power wiring.
03 Thermocouple Types Chart
The letter names come from international standards (ASTM E230 in North America and IEC 60584 internationally). Ranges below are typical working ranges; exact limits depend on wire size, sheath and environment.
| Type | Metals (+ / β) | Typical range | Sensitivity | Best for |
|---|---|---|---|---|
| K | Chromel / Alumel (nickel-chromium / nickel-aluminium) | β200 to 1250 Β°C | ~41 Β΅V/Β°C | General purpose, most industrial uses |
| J | Iron / Constantan | 0 to 750 Β°C | ~52 Β΅V/Β°C | Plastics, older equipment, vacuum or reducing atmospheres |
| T | Copper / Constantan | β200 to 350 Β°C | ~43 Β΅V/Β°C | Cryogenics, food, labs |
| E | Chromel / Constantan | β200 to 900 Β°C | ~68 Β΅V/Β°C | Highest signal, low temperatures |
| N | Nicrosil / Nisil | β200 to 1250 Β°C | ~39 Β΅V/Β°C | Stable high-temperature use, replaces K |
| R | Platinum-13% rhodium / Platinum | 0 to 1450 Β°C | ~10 Β΅V/Β°C | Furnaces, glass, high accuracy |
| S | Platinum-10% rhodium / Platinum | 0 to 1450 Β°C | ~10 Β΅V/Β°C | Furnaces, calibration, labs |
| B | Platinum-30% rhodium / Platinum-6% rhodium | 600 to 1700 Β°C | ~10 Β΅V/Β°C | Very high temperatures: steel, glass, ceramics |
Types K, J, T, E and N are called base metal thermocouples: low cost and widely used. Types R, S and B are noble metal thermocouples: they contain platinum, cost much more, and are used where temperatures are too high for base metals.
04 Each Thermocouple Type Explained
Type K thermocouple
The most common thermocouple in the world. Wide range, low cost and good resistance to oxidation. If you are not sure which type to use, Type K is usually the safe starting point. Its weak points are drift after long periods above about 1000 Β°C and errors in some reducing atmospheres.
Type J thermocouple
Higher output than K but a smaller range. The iron wire rusts in moist, oxidising conditions, so Type J is mostly used below about 750 Β°C, in plastics machinery and in older equipment that was designed for it.
Type T thermocouple
The best base metal choice for low and sub-zero temperatures. It is stable and accurate in cold storage, food processing and lab work, but limited to about 350 Β°C because the copper wire oxidises.
Type E thermocouple
Gives the highest output per degree of any common type, which makes small temperature changes easier to detect. Good for low temperatures and non-magnetic applications.
Type N thermocouple
Developed as an improved Type K. It drifts less at high temperatures and is more stable over time, so it is often chosen for long-running furnaces and heat-treatment lines.
Types R and S thermocouples
Platinum-based types with excellent accuracy and stability at high temperatures. Type S has long been used as a reference standard in calibration. Both are expensive and have low output, so they need good instruments.
Type B thermocouple
Made for the hottest applications, up to about 1700 Β°C. Its output is almost zero below about 50 Β°C, so it is not used for low readings, but it does not need careful cold junction compensation at normal room temperature.
05 Thermocouple Colour Codes
Thermocouple wire is colour coded so that each type and each leg can be identified. Two systems are common: the North American ANSI/ASTM code and the international IEC 60584-3 code. In the ANSI code, the negative leg is always red. In the IEC code, the negative leg is always white.
| Type | ANSI: + leg | ANSI: β leg | IEC: + leg (and jacket) | IEC: β leg |
|---|---|---|---|---|
| K | Yellow | Red | Green | White |
| J | White | Red | Black | White |
| T | Blue | Red | Brown | White |
| E | Purple | Red | Violet | White |
| N | Orange | Red | Pink | White |
Check which code your site uses. Red means negative in the ANSI system, but in older national codes red was sometimes used for a positive leg. Mixing up codes, or swapping the legs, gives readings that move the wrong way when the temperature changes.
06 Junction Types: Grounded, Ungrounded and Exposed
Most industrial thermocouples are sealed inside a metal sheath. How the hot junction sits inside that sheath changes the speed and the noise performance.
Grounded junction
The junction is welded to the sheath tip. It responds quickly, but it connects the sensor to earth, which can cause ground loops and noise on some instruments.
Ungrounded junction
The junction is insulated from the sheath. It is a little slower but electrically isolated, which is why it is the usual choice for PLC and DCS inputs.
Exposed junction
The junction sticks out of the sheath. It is the fastest, but it has no protection, so it is only used for clean, non-corrosive gases such as air.
07 How to Choose the Right Thermocouple Type
Ask these questions in order:
- What is the maximum temperature? Above about 1250 Β°C you need R, S or B. Below that, a base metal type will usually do.
- Will it measure below 0 Β°C? Type T or E is the better choice for cold measurements.
- What is the atmosphere? Oxidising, reducing, vacuum or corrosive conditions all affect wire life. Check the manufacturer's guidance.
- How much accuracy and stability do you need? For long-term stability at high heat, N beats K. For the best accuracy, use R or S, or consider an RTD at lower temperatures.
- What does the existing system expect? Many controllers and PLC cards are set up for one type. Replacing like with like avoids mistakes.
- What is the budget? Platinum types can cost many times more than K or J.
Simple rule: start with Type K. Move to T for cold work, N for long-term high heat, and R, S or B for furnaces above about 1250 Β°C.
08 Thermocouple vs RTD
The other common industrial temperature sensor is the RTD (resistance temperature detector), usually a Pt100. Here is how they compare.
| Feature | Thermocouple | RTD (Pt100) |
|---|---|---|
| Temperature range | Very wide, up to about 1700 Β°C | Usually β200 to about 600 Β°C |
| Accuracy and stability | Good | Better |
| Response speed | Fast, especially with small junctions | Slower |
| Durability | Very rugged, handles vibration | More fragile element |
| Cost | Low (base metal types) | Higher |
| Needs power? | No, it generates its own voltage | Yes, a small excitation current |
In short: use an RTD when you need the best accuracy at moderate temperatures, and a thermocouple when you need high temperatures, fast response or a rugged, low-cost sensor.
09 Connecting a Thermocouple to a PLC
In a control system, the thermocouple reading usually goes to a PLC, DCS or temperature controller. There are two common ways to connect it.
Direct to a thermocouple input module
Wire the sensor, or its extension wire, straight to a PLC thermocouple card. In the hardware configuration, select the correct type (K, J, T and so on) and units. The card handles cold junction compensation and linearisation.
Through a 4β20 mA transmitter
A head-mounted or DIN-rail transmitter converts the millivolt signal to 4β20 mA near the sensor. This is better for long cable runs and noisy areas, and connects to a standard analog input.
Once the temperature is in the PLC, it is used in logic just like any other value: compare it with a setpoint, raise an alarm, or feed a PID loop. If you are learning PLC programming, our guide to ladder logic and the free book PLC Pulse show how analog inputs fit into a program. For safety-related temperature trips, the risk assessment principles in our ISO 12100 guide apply.
10 Common Mistakes
Wrong type selected in the instrument
A Type J sensor read as Type K gives a wrong temperature that still looks believable. Always match the configuration to the sensor.
Using copper wire for the run
Ordinary copper cable creates new junctions and errors. Use thermocouple wire or the matching extension or compensating cable all the way to the terminals.
Reversed polarity
Swapped legs make the reading fall when the temperature rises. Check the colour code before terminating.
Running signal wires next to power cables
Millivolt signals pick up noise easily. Use shielded cable, earth the shield at one end, and keep it away from motor and VFD cables.
Ignoring drift
Thermocouples drift over time, especially at high temperatures. Check them against a reference on a regular schedule and replace them when needed.
Want to Build Practical Automation Skills?
Dr. Ahsan Rahman offers training and consulting in industrial automation, PLCs, instrumentation and control systems for companies and engineering programs.
See Engineering Services β11 Frequently Asked Questions
What are the main types of thermocouple?
The main thermocouple types are K, J, T, E and N, which are base metal types, and R, S and B, which are platinum-based noble metal types. Type K is the most common for general industrial use.
Which thermocouple type is most commonly used?
Type K is the most commonly used thermocouple. It covers roughly β200 to 1250 Β°C, costs little, resists oxidation and works with almost every controller and PLC input card.
What is the difference between Type K and Type J thermocouples?
Type K uses nickel-chromium and nickel-aluminium wires and works up to about 1250 Β°C. Type J uses iron and constantan, gives a slightly higher signal, and is normally limited to about 750 Β°C because the iron wire oxidises. The two are not interchangeable without changing the instrument setting.
Which thermocouple is best for high temperatures?
For temperatures up to about 1250 Β°C, Type K or Type N work well, with N being more stable over time. Above that, platinum types are used: R and S up to about 1450 Β°C, and Type B up to about 1700 Β°C.
What is cold junction compensation?
A thermocouple measures the temperature difference between its hot junction and the point where it connects to the instrument, called the cold junction. Cold junction compensation measures the temperature at the instrument terminals and adds it, so the reading shows the true process temperature.
Is a thermocouple better than an RTD?
It depends on the job. Thermocouples cover much higher temperatures, respond faster and are more rugged and cheaper. RTDs are more accurate and stable at moderate temperatures, usually below about 600 Β°C.
Can I connect a thermocouple directly to a PLC?
Yes, if the PLC has a thermocouple input module. You select the thermocouple type in the configuration and the module handles cold junction compensation. For long cable runs or noisy areas, a 4β20 mA temperature transmitter connected to a standard analog input is often a better choice.
β Final Thoughts
Thermocouples are simple sensors, but the type you choose decides how accurate, stable and long-lasting your measurement will be. Match the type to the temperature range and atmosphere, use the right wire all the way to the instrument, and set the instrument to the same type.
Get those three things right and a thermocouple will give years of reliable service, from a freezer to a furnace.
Try this: find one temperature reading at your workplace or lab and trace it back. What thermocouple type is it, what colour is the wire, and what type is set in the controller or PLC? If they do not match, you have found your first fault.
Written by Dr. Ahsan Rahman, PhD, P.E.
Dr. Ahsan Rahman is an Associate Professor and Head of Electrical Engineering at the University of Prince Mugrin and a licensed Professional Engineer. He specialises in control systems, mechatronics and industrial automation, and is the author of free online books on PLC programming, engineering safety and risk assessment. Learn more β Β· Contact β
Subscribe to our newsletter
Get an email when a new article or free book is published. No spam, unsubscribe any time.